![集中式电能质量智能优化装置 集中式电能质量智能优化装置]()
1, product introduction
The centralized power quality intelligent optimization device (BPF) is installed at the head of the transformer to realize the balance of the output power of the three phases of the transformer, compensate the reactive current and harmonic current generated by the distribution line, and improve the carrying capacity of the transformer. Adjust the output of the transformer Voltage, to ensure the quality of power supply.
2, working principle
BPF (Balance Power Filter) adopts advanced three-level circuit topology (low loss, low noise), through the three-phase line asymmetric active power energy exchange and current compensation technology to achieve three Phase power balance, reactive power compensation and harmonic current elimination.
![集中式电能质量智能优化装置 集中式电能质量智能优化装置]()
3, Features
Three-phase unbalanced management: three-phase intelligent regulation of active power, to achieve three-phase transformer current balance output; to avoid when the load is unbalanced distribution, resulting in single-phase transformer overload; the same time, three-phase balanced output can effectively reduce transformer losses.
Power factor adjustment: Compared with the traditional capacitor compensation, the device real-time tracking high-speed changes in load reactive power, accurate tracking compensation, and can effectively suppress the harmonic voltage and current systems. By adjusting the reactive power, system voltage fluctuations can be reduced.
Filter function: Multi-DSP collaborative control, high filtering accuracy, fast response; the target harmonic, the effective filtering capacity of up to 95%, while filtering a variety of harmonics, the maximum can be filtered to the 50th harmonic; Settable harmonic fractional compensation.
Modular design: Taking into account the growth of the user load characteristics, the device uses a modular design. Customers can configure the capacity according to different needs, the need for expansion or replacement, the increase or decrease can be easily replaced, thereby reducing duplication of investment.
Structural Design: The device supports outdoor pillar installation or indoor installation, the protection grade is IP54, which can be installed on the existing poles or distribution room.
Communication system design: Equipment with RS232 / 485 and GPRS interface, access to power system ACADA system, real-time monitoring of power grid voltage, current, power and other state, to achieve the daily maintenance of equipment and management.
Extended functions: The device is reserved for the I / O interface, on-load regulator, compensation capacitor bank and other equipment for integrated control.
4、技术参数
主要技术参数 |
参数名称 | 参数 | 参数说明 |
交流输入 | 工作相电压 | 120V~260V | 电网电压允许不对称 |
电气接线 | 三相四线 | TN-S母线(独立的N线和PE线) |
工作电压频率 | 50Hz±1% |
|
技术指标 | 额定容量 | 容量(Kvar) | 30~100 | 无功补偿模式 |
电流(A) | 50~150 | 谐波补偿功能有功不平衡调节模式 |
功率(KW) | 30~100 | 有功不平衡调节模式 |
TSC接口 | ≥8路高速接口 | 可控制电容器组的投切 |
多路高速I/O口 | ≥4路干节点 | 可与有载调压相结合,具备控制分接头调节能力 |
损耗 | <3% |
|
开关频率 | ≥20KHz |
|
全响应时间 | <10ms |
|
性能指标 | 谐波消除能力 | ≥95% |
|
补偿后系统功率因素 | ≥0.96 |
|
有功不平衡补偿后不对称度 | <5% |
|
环境条件 | 环境温度 | ﹣30~55℃ |
|
相对湿度 | <95%RH 无凝露 |
|
冷却方式 | 强制风冷 |
|
海拔高度 | 2000m | 超出2000m后每100m降额1%运行 |
安装方式 | 户外式柱上安装或壁挂式安装;户内式壁挂式安装 |
|
通讯接口 | 标准RS232/485接口、以太网接口、电力线载波与积木式结构 |
|
扩展能力 | 最多12台设备并联 |
|
防护等级 | 不低于IP54 |
|
噪音 | ≤60dB |
|
可有效工作时间 | MTBF≥10万小时 |
|
后台监控 | 具备完善的、开放的后台监控系统 |
5、产品列表
安装方式 | 线制 | 可选容量范围 | 标准型号产品 |
户外式 | 3P4L/3P3L | 0~75KVA | SYICD-BPF 0.4/30-Z |
SYICD-BPF 0.4/50-Z |
SYICD-BPF 0.4/75-Z |
户内式 | 3P4L/3P3L | 0~75KVA | SYICD-BPF 0.4/30-I |
SYICD-BPF 0.4/50-I |
SYICD-BPF 0.4/75-I |
6、型号命名
![集中式电能质量智能优化装置 集中式电能质量智能优化装置]()