hotline: 0757-27881769(Hotline) 0757-27830137(Support)
Products product details
Product name:

Centralized power quality intelligent optimization device

listing date: 2017-11-18
Products / Related products
2017 - 11 - 21
Highlight FeaturesHigh Irms RatingHigh Ipeak RatingLow self-inductanceHigh reliability and life expectancyNon-polar技术参数Paramaters产品型号SpecificationDCLJCSY 900-700额定电容Rated Capacitance700uF(25℃)额定电压Rate...
2017 - 10 - 13
Execution standard: Meet the requirement of standard《IEC I: 60252-1-2013》《UL810-2008》《GB3667.1-2016》; Product features:low in dissipation,small inherent temperature rise,long life ...
2017 - 11 - 22
Standard:《UL810-2008》《IEC 60252-1:2013》《GB/T 3667.1-2016》.Feature: Low dissipation factor,Low temperature rise,Long service life,Excellent self-healing property,Stable capacitance,Inner explosion...
Product features

集中式电能质量智能优化装置

1, product introduction

     The centralized power quality intelligent optimization device (BPF) is installed at the head of the transformer to realize the balance of the output power of the three phases of the transformer, compensate the reactive current and harmonic current generated by the distribution line, and improve the carrying capacity of the transformer. Adjust the output of the transformer Voltage, to ensure the quality of power supply.

2, working principle

BPF (Balance Power Filter) adopts advanced three-level circuit topology (low loss, low noise), through the three-phase line asymmetric active power energy exchange and current compensation technology to achieve three Phase power balance, reactive power compensation and harmonic current elimination.


集中式电能质量智能优化装置

3, Features

Three-phase unbalanced management: three-phase intelligent regulation of active power, to achieve three-phase transformer current balance output; to avoid when the load is unbalanced distribution, resulting in single-phase transformer overload; the same time, three-phase balanced output can effectively reduce transformer losses.

 

Power factor adjustment: Compared with the traditional capacitor compensation, the device real-time tracking of high-speed changes in load reactive power, accurate tracking compensation, and can effectively suppress the system of harmonic voltage and current. By adjusting the reactive power, system voltage fluctuations can be reduced.

 

Filter function: Multi-DSP collaborative control, high filtering accuracy, fast response; the target harmonic, the effective filtering capacity of up to 95%, while filtering a variety of harmonics, the maximum can be filtered to the 50th harmonic; Settable harmonic fractional compensation.

 

Modular design: Taking into account the growth of the user load characteristics, the device uses a modular design. Customers can configure the capacity according to different needs, the need for expansion or replacement, the increase or decrease can be easily replaced, thereby reducing duplication of investment.

 

Structural Design: The device supports outdoor pillar installation or indoor installation, the protection grade is IP54, which can be installed on the existing poles or distribution room.

 

Communication system design: Equipment with RS232 / 485 and GPRS interface, access to power system ACADA system, real-time monitoring of power grid voltage, current, power and other state, to achieve the daily maintenance of equipment and management.

 

Extended functions: The device is reserved for the I / O interface, on-load regulator, compensation capacitor bank and other equipment for integrated control.


4.technical parameters

Can work effectively

The main technical parameters

parameter name

parameter

Parameter Description

AC input

Working phase voltage

120V~260V

Grid voltage to allow asymmetry

Electrical wiring

Three-phase four-wire

TN-S bus (independent N and PE lines)

Operating voltage and frequency

50Hz±1%


Technical indicators

Rated Capacity

capacity(Kvar)

30~100

Reactive power compensation mode

Current(A)

50~150

Harmonic compensation function Active imbalance adjustment mode

power(KW)

30~100

Active imbalance adjustment mode

TSC interface

≥8 high-speed interface

Can control the switching of capacitor bank

Multi-channel high-speed I / O port

≥4 road dry node

Can be combined with on-load regulation, with control tap adjustment capability

loss

<3%


On-off level

≥20KHz


Full response time

<10ms


Performance

Harmonic elimination capability

≥95%


System power factor after compensation

≥0.96


Asymmetric imbalance after compensation

<5%


Environmental conditions

Ambient temperature

﹣30~55℃


Relative humidity

<95%RH No condensation


cooling method

Forced air cooling


Altitude

2000m

Exceeds 2000m and derates 1% for every 100m

Installation method

Outdoor column installation or wall-mounted installation; indoor wall-mounted installation


Communication Interface

Standard RS232 / 485 interface, Ethernet interface, power line carrier and building block structure


Expand ability

Up to 12 devices in parallel


Degree of protection

Not less than IP54


noise

≤60dB


MTBF≥100,000 hours





Background monitoring

Have a sound, open background monitoring system

 

5. product list

Installation method

Line system

Optional capacity range

Standard model products

Outdoor

3P4L/3P3L

0~75KVA

SYICD-BPF 0.4/30-Z

SYICD-BPF 0.4/50-Z

SYICD-BPF 0.4/75-Z

Indoor

3P4L/3P3L

0~75KVA

SYICD-BPF 0.4/30-I

SYICD-BPF 0.4/50-I

SYICD-BPF 0.4/75-I


6.model name

集中式电能质量智能优化装置


last:nullnext:null
Product parameters
佛山市顺德区胜业电气有限公司
Scan
access to mobile phone cloud web site
Contact us
Copyright ©2017 - 2020 Foshan Shunde District Sheng Ye Electric Co., Ltd.
犀牛云提供企业云服务
犀牛云提供云计算服务
Address: 4th Road,Lunjiao Town,Shunde Foshan City,Guangdong Provinec,China
Phone:0757—27881769
fax:+86 0755-2788 8009
Zip code:330520